Draw out MCC/Drawout switchboard/low voltage drawout switchgear/MNS drawout switchgear

Location:
ry/Region:, China ( Mainland)
Status:
New
Sample Availibility:
yes
Payment Terms:
Cash, Bank Transfer, Letter of Credit, T/T, L/C

Product Description

Draw out MCC/Drawout switchboard/low voltage drawout switchgear/MNS drawout switchgear

MNS is modularized, multi-functional drawout MCC, which is applicable to metallurgy, petroleum, chemical industrial, industrial and mining enterprises and all the situations high reliable drawout MCC , distribution system and motor control system are needed.

MNS series drawout MCC can meet your need completely. It is applicable to all drawout MCC of the current 4000A or below.

drawout MCC Standards

Execution standard: IEC60439-1, GB7251.1.

drawout MCC Advantages

1. Panel board with compact structure, save the volume of cabinet body.

2. The panel board can be arranged back to back

3. The panel board body can meet the requirements of earthquake resistance, oscillation resistance and shock resistance

4. It can be built up into different modes freely, such as fixed type and draw-out type

5. Corresponding protection class of the panel board body could be designed according to the different requirements of the job and environment.

6. Select and using standard component entirely, convenient for the design of project planner.

7. The arrangement of power distribution circuit is economic

8. With anti electric arc design

9. Convenient for equipment upgrade and inprovement

10. The panel board is free of maintenance to the most extent.

11. Safe for the opeartor

12. Reliable enough and high flexibility.

drawout MCC Installation dimension

1. The fixed cabinet:

Width: 600mm, 800mm, 1000mm

Depth: 600mm, 800mm, 1000mm

2. The withdrawable cabinet:

Width: 600mm, 800mm, 900mm, 1000mm(600mm not suggested)

Depth: 600mm, 800mm, 1000mm(600mm not suggested)

3. The fixed isolating cabinet

Width: 600mm, 900mm, 1000mm

Depth: 600mm, 800mm, 1000mm

Rated operational voltage

690V/AC

Rated insulation voltage

1000V/AC

Rated frequency

50/60hz

Grounding system

TT,IT, TN-S,TN-C-S

Ratd voltage of auxiliary circuit

AC380,220v/ DC220v

Maximum coil in and out broken circuit

4000A

Pollution degree

3

Rated current

4000A

Horizontal busbar rated current

4000A

Vertical busbar rated current

2000A,1000A

Horizontal busbar ratd shorttime withstand current

50/80KA

Horizontal busbar rated peak value withstand current

105/176KA

Vertical busbar rated short time withstand current

50KA

Vertical busbar rated peak value withstand current

105KA

MNS is modularized, multi-functional Draw out MCC . Electric cabinets, 220V,380V switchgear,switch cabinet .

Please provide the following data :
a. Name, specification, type, quantity, delivery date of product, rated voltage of fuse ;
b. diagrams and list of compoments



This member's information has NOT been authenticated or verified by importexportleads.net or any third party. Only Gold Members have completed an authentication and verification procedure conducted by third-party credit agencies.

For more information on importexportleads Gold Membership, Click here

Contact Information

Company:
 Tangshan Dunshi Electric Co., Ltd.
Phone Number:
  gion:China (Mainland)Country/Region:end
Fax Number: